WHD20R-11 Temperature & Humidity Controller

Paired with 1 Sensor One Channel Temperature & Humidity

WHD series smart temperature and humidity controller is suitable for adjustment and control of temperature and humidity in equipments of high voltage switchgear, terminal box, ring network panel, box transformer substation etc. It can effectively protect relevant equipment from faults resulting from excessive low or high temperature, creepage or flashover etc. from humidity or condensation.

WHD20R-11.4.png
             

Main Feature 

● Temperature: -40.0℃~+99.9℃

● Humidity: 20%RH~90%RH

● Control: one channel temperature&humidity

● Power supply: AC 85~265V DC 100~350V

● Analog output: DC 4~20mA

● Communication: RS485

 


Overview


Parameter

Technical Parameter
Value
Measuring range
Temperature
-40.0℃~+99.9℃
Humidity
20%RH~90%RH
Accuracy
Temperature
±1℃
Humidity
±5%RH
Analog output
DC 4~20mA
Set range of controlling parameter
Heating for Temperature rising
-40.0℃~40.0℃
Blowing for temperature decreasing
0℃~99.9℃
Humidity control
20%RH~90%RH
Contact capacity
5A/AC250V
Communication
RS485(MODBUS-RTU)
Auxiliary power supply
Working range
AC 85~265V, DC 100~350V
Consumption
Basic power consumption (≤0.8w)
Relay power consumption (each channel ≤0.7w)
Insulation resistance
≥100MΩ
Environment
Temperature
-20℃~+60℃
Humidity
≤95%RH(No condensation)
Altitude
≤2500m

 


Wiring

 

 


Network


Package

MINIMUM PACKAGE

 

 

MINIMUM PAKAGE

Package dimensions(1 PC)

170*150*130mm

Pakage Weight(1 PC)

0.5Kg

 

WHOLE BOX PAKAGE

 

Package dimensions(36 PCS)

450*240*250mm

Pakage Weight(36 PCS)

18.5kG

 

PRODUCT HS CODE

 

9028301400

 


FAQ

Q: Connect users between the sensor and the controller, can it be matched? How long is the length in meters?

A: The user can match, but it is required to use a 4-core shielded wire, and a 2.5-meter shielded wire is attached to the factory. The longest distance between the sensor and the controller is 20 meters.

 

Q: Can WHD switch control manually and automatically?

A: Yes, but be sure to explain to the customer service before placing an order. It is an abnormal operation.

 

Q: User have their own sensor,can they buy a controller?

A: No, the sensor and controller need to be used together. 2 device can not sold separately.

 

 


Application


Hot Products

Acrel ADW600 Multi Channels Smart 3 Phase Energy Meter

Optional 4DI2DO,12 channels temp measure,4 channels Residual current monitoring

AM6 Prefabricated Substation Protection & Control Device

2 × 4–20 mA DC measurement channels and 3 temperature measurement channels

ATU Intelligent Monitoring Terminal for Switchgear

Conduct centralized monitoring and management.

AMC300L Base Station AC Multi-loop Intelligent Power Collection and Monitoring Device

6 channel 3 phase or 18 channel 1 phase

Acrel ADW600 Multi Channels Smart 3 Phase Energy Meter

With Different Size of CTs,easy to install D10,D16,D24,D36

Acrel ADW600 Multi Channels Smart 3 Phase Energy Meter

Optional 4DI2DO,12 channels temp measure,4 channels Residual current monitoring

AM6 Prefabricated Substation Protection & Control Device

2 × 4–20 mA DC measurement channels and 3 temperature measurement channels

ATU Intelligent Monitoring Terminal for Switchgear

Conduct centralized monitoring and management.

AMC300L Base Station AC Multi-loop Intelligent Power Collection and Monitoring Device

6 channel 3 phase or 18 channel 1 phase

Acrel ADW600 Multi Channels Smart 3 Phase Energy Meter

With Different Size of CTs,easy to install D10,D16,D24,D36

Acrel ADW600 Multi Channels Smart 3 Phase Energy Meter

Optional 4DI2DO,12 channels temp measure,4 channels Residual current monitoring

AM6 Prefabricated Substation Protection & Control Device

2 × 4–20 mA DC measurement channels and 3 temperature measurement channels

ATU Intelligent Monitoring Terminal for Switchgear

Conduct centralized monitoring and management.